نقد و بررسی : Analog Input Module 6ES7134-6JD00-0CA1
Analog Input Module 6ES7134-6JD00-0CA1
SIMATIC SIEMENS ET 200SP, Analog input module , AI 4xRTD/TC High Feature, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.1%, 2-/3-/4-wire
SIEMENS | |
General information |
|
Product type designation | AI 4x RTD/TC 2/3/4-wire HF, PU 1 |
HW functional status | From FS08 |
Firmware version
● FW update possible |
Yes |
usable BaseUnits | BU type A0, A1 |
Color code for module-specific color identification plate | CC00 |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Adjustment of measuring range | Yes |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated as of version | V14 |
● STEP 7 configurable/integrated as of version | V5.6 |
● PCS 7 configurable/integrated as of version | V8.1 SP1 |
● PROFIBUS as of GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 |
Operating mode |
● Oversampling | No
No |
● MSI | |
CiR – Configuration in RUN | |
Reparameterization possible in RUN | Yes |
Calibration possible in RUN | Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption, max. | 35 mA |
Power loss | |
Power loss, typ. | 0.75 W |
Address area |
|
Address space per module | |
● Address space per module, max. | 8 byte; + 1 byte for QI information |
Hardware configuration | |
Automatic encoding | Yes |
● Mechanical coding element | Yes |
Selection of BaseUnit for connection variants | |
● 2-wire connection | BU type A0, A1 |
● 3-wire connection | BU type A0, A1 |
Analog inputs |
|
Number of analog inputs | 4 |
permissible input voltage for voltage input (destruction limit), max. | 30 V |
Cycle time (all channels), min. | Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary |
Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
Input ranges (rated values), voltages | |
● -1 V to +1 V | Yes; 16 bit incl. sign |
● Input resistance (-1 V to +1 V) | 1 MΩ |
● -250 mV to +250 mV | Yes; 16 bit incl. sign |
● Input resistance (-250 mV to +250 mV) | 1 MΩ |
● -50 mV to +50 mV | Yes; 16 bit incl. sign
1 MΩ |
● Input resistance (-50 mV to +50 mV) |
● Input resistance (Ni 500) | 1 MΩ
Yes; 16 bit incl. sign |
● Pt 100 | |
● Input resistance (Pt 100) | 1 MΩ |
● Pt 1000 | Yes; 16 bit incl. sign |
● Input resistance (Pt 1000) | 1 MΩ |
● Pt 200 | Yes; 16 bit incl. sign |
● Input resistance (Pt 200) | 1 MΩ |
● Pt 500 | Yes; 16 bit incl. sign |
● Input resistance (Pt 500) | 1 MΩ |
Input ranges (rated values), resistors | |
● 0 to 150 ohms | Yes; 15 bit |
● Input resistance (0 to 150 ohms) | 1 MΩ |
● 0 to 300 ohms | Yes; 15 bit |
● Input resistance (0 to 300 ohms) | 1 MΩ |
● 0 to 600 ohms | Yes; 15 bit |
● Input resistance (0 to 600 ohms) | 1 MΩ |
● 0 to 3000 ohms | Yes; 15 bit |
● Input resistance (0 to 3000 ohms) | 1 MΩ |
● 0 to 6000 ohms | Yes; 15 bit |
● Input resistance (0 to 6000 ohms) | 1 MΩ |
● PTC | Yes; 15 bit |
● Input resistance (PTC) | 1 MΩ |
Thermocouple (TC) | |
Temperature compensation | |
— parameterizable | Yes |
— Reference channel of the module | Yes |
— internal comparison point | Yes; with BaseUnit type A1 |
— Reference channel of the group | Yes |
— Number of reference channel groups | 4; Group 0 to 3 |
— fixed reference temperature | Yes |
Cable length |
|
● shielded, max. | 200 m; 50 m with thermocouples |
Analog value generation for the inputs | |
Measurement principle | integrating (Sigma-Delta) |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 16 bit |
● Integration time, parameterizable | Yes |
● Basic conversion time, including integration time (ms) |
— additional processing time for wire-break check | 2 ms; In the ranges resistance thermometers, resistors and thermocouples
2 ms; for 3/4 wire transducer (resistance thermometer and resistor) |
— additional power line wire-break check | |
● Interference voltage suppression for interference frequency f1 in Hz | 16.6 / 50 / 60 Hz |
● Conversion time (per channel) | 180 / 60 / 50 ms |
Smoothing of measured values | |
● Number of smoothing levels | 4; None; 4/8/16 times |
● parameterizable | Yes |
Encoder | |
Connection of signal encoders | |
● for voltage measurement | Yes |
● for resistance measurement with two-wire connection | Yes |
● for resistance measurement with three-wire connection | Yes |
● for resistance measurement with four-wire connection | Yes |
Errors/accuracies | |
Linearity error (relative to input range), (+/-) | 0.01 %; ±0.1 % for resistance thermometers and resistance |
Temperature error (relative to input range), (+/-) | 0.0009 %/K; ±0.005 % / K at thermocouple |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range | |
● Voltage, relative to input range, (+/-) | 0.1 % |
● Resistance, relative to input range, (+/-) | 0.1 % |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to input range, (+/-) | 0.05 % |
● Resistance, relative to input range, (+/-) | 0.05 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
● Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
● Common mode voltage, max. | 10 V |
● Common mode interference, min. | 90 dB |
Isochronous mode |
|
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Alarms |
● Diagnostic alarm | Yes
Yes; two upper and two lower limit values in each case |
● Limit value alarm | |
Diagnostic messages | |
● Monitoring the supply voltage | Yes |
● Wire-break | Yes; channel by channel |
● Group error | Yes |
● Overflow/underflow | Yes; channel by channel |
Diagnostics indication LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; Green PWR LED |
● Channel status display | Yes; Green LED |
● for channel diagnostics | Yes; Red LED |
● for module diagnostics | Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
● between the channels | No |
● between the channels and backplane bus | Yes |
● between the channels and the power supply of the electronics | Yes |
Isolation |
|
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | -30 °C |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | -30 °C |
● vertical installation, max. | 50 °C |
Altitude during operation relating to sea level | |
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
last modified: | 01/20/2020 |
SIEMENS Analog Input Module 6ES7134-6JD00-0CA1
-
پنل لمسی 9.7 اینچ HMI WEINTEK
تماس بگیریدنل لمسی (اچ ام ای) 9.7 اینچ وینتک (WEINTEK HMI) با رزولوشن 1024*768 ساخته شده است. HMI وینتک سری MT8092XE دارای صفحه نمایش از نوع TFT LCD همراه با نور پس زمینه LED می باشد. پردازنده به کار رفته در این پنل لمسی Cortex-A8 با فرکانس 1 گیگا هرتز و از نوع 32 بیتی می باشد. حافظه رم (RAM) در این HMI ، 256 MB می باشد. همچنین حافظه فلش… -
شارژر 12 ولت 24.3 آمپر مین ول
0 تومانشارژر 12 ولت 24.3 آمپر مین ول با توان اندازه گیری شده 360 وات در خروجی محاسبه شده است. این منبع تغذیه در دسته پاور های کف خواب شرکت مین ول قرار می گیرد. از جمله ویژگی های حفاظتی این محصول می توان به حفاظت در برابر اتصال کوتاه، اضافه جریان، اضافه ولتاژ، حفاظت از باتری و دمای بالا اشاره کرد. شارژر برای باتری های اسید سرب (سیل، ژل و… -
منبع تغذیه 24 ولت 6.5 آمپر مین ول
790,000 تومانمنبع تغذیه 24 ولت 6.5 آمپر مین ول (LRS-150-24) با توان 150 وات اندازه گیری شده است.این منبع تغذیه دارای طراحی باریک با ضخامت 30 میلی متر می باشد. بازدهی در این منبع تغذیه تا 87.5% می رسد. توان مصرفی در این منبع تغذیه در زمان بی باری بسیار کم و به عدد 0.5 وات میرسد. منبع تغذیه LRS-150 توانایی مقاومت در برابر افزایش ولتاژ ورودی تا 300 ولت را… -
منبع تغذیه 5 ولت 3 آمپر مین ول
0 تومانمنبع تغذیه 5 ولت 3 آمپر مین ول با توان 30 وات واقعی و تحویلی به مصرف کننده ساخته شده است. این منبع تغذیه جزء محصولات ریلی شرکت مین ول محسوب می شود. پاور 5 ولت مین ول در دسته اقتصادی محصولات این شرکت تایوانی قرار می گیرد. راندمان این منبع تغذیه به عدد بالای 89% می رسد که در نوع خود بسیار خوب و کارآمد است. تلفات توان در… -
منبع تغذیه 12 ولت 50 آمپر مین ول
4,500,000 تومانمنبع تغذیه 12 ولت 50 آمپر مین ول با توان و قدرت 600 وات واقعی اندازه گیری شده است. این منبع تغذیه سوئیچینگ در دسته محصولات کف خواب این شرکت تایوانی قرار می گیرد. راندمان در این منبع تغذیه به عدد بالای 88% می رسد که به راحتی پاسخگوی نیاز کار می باشد. از ویژگی های حفاظتی در این منبع تغذیه می توان به حفاظت در برابر اتصال كوتاه، اضافه… -
سنسور القایی OMRON E2B-M12LN08-M1-B1 امرن
تماس بگیرید◀️ نوع محصول : سنسور امرن / القایی / مجاورتی ◀️ قطر سنسور : استوانه ای قطر 12 ◀️ خروجی سنسور : PNP NO