Analog Input Module 6ES7134-6JD00-0CA1

Analog Input Module 6ES7134-6JD00-0CA1


تماس بگیرید

بررسی اجمالی محصول

SIMATIC ET 200SP, Analog input module, AI 4xRTD/TC High Feature, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.1%, 2-/3-/4-wire

جهت ارائه خدمات همکاری از قبیل تخفیف همکاری , لیست قیمت و…

خدمات همکاری آی سی اِس شاپـــــــ شامل تامین لوازم و تجهیزات صنعتی (برندهای مطرح دنیا) ، ارائه گارانتی و تعمیر فوری محصولات , مشاوره به همکاران گرامی , ارائه تخفیف همکاری و یا ارسال رایگان محصولات می باشد . (همکاری شمارتو وارد کن تا فرم ثبت نام برات ارسال بشه )

نقد و بررسی : Analog Input Module 6ES7134-6JD00-0CA1

Analog Input Module 6ES7134-6JD00-0CA1

SIMATIC SIEMENS ET 200SP, Analog input module , AI 4xRTD/TC High Feature, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.1%, 2-/3-/4-wire

SIEMENS

General information

Product type designation AI 4x RTD/TC 2/3/4-wire HF, PU 1
HW functional status From FS08
Firmware version

● FW update possible

Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification plate CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Adjustment of measuring range Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated as of version V14
● STEP 7 configurable/integrated as of version V5.6
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No

No

● MSI
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 35 mA
Power loss
Power loss, typ. 0.75 W

Address area

Address space per module
● Address space per module, max. 8 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 2-wire connection BU type A0, A1
● 3-wire connection BU type A0, A1

Analog inputs

Number of analog inputs 4
permissible input voltage for voltage input (destruction limit), max. 30 V
Cycle time (all channels), min. Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary
Technical unit for temperature measurement adjustable Yes; °C/°F/K
Input ranges (rated values), voltages
● -1 V to +1 V Yes; 16 bit incl. sign
● Input resistance (-1 V to +1 V) 1 MΩ
● -250 mV to +250 mV Yes; 16 bit incl. sign
● Input resistance (-250 mV to +250 mV) 1 MΩ
● -50 mV to +50 mV Yes; 16 bit incl. sign

1 MΩ

● Input resistance (-50 mV to +50 mV)
● Input resistance (Ni 500) 1 MΩ

Yes; 16 bit incl. sign

● Pt 100
● Input resistance (Pt 100) 1 MΩ
● Pt 1000 Yes; 16 bit incl. sign
● Input resistance (Pt 1000) 1 MΩ
● Pt 200 Yes; 16 bit incl. sign
● Input resistance (Pt 200) 1 MΩ
● Pt 500 Yes; 16 bit incl. sign
● Input resistance (Pt 500) 1 MΩ
Input ranges (rated values), resistors
● 0 to 150 ohms Yes; 15 bit
● Input resistance (0 to 150 ohms) 1 MΩ
● 0 to 300 ohms Yes; 15 bit
● Input resistance (0 to 300 ohms) 1 MΩ
● 0 to 600 ohms Yes; 15 bit
● Input resistance (0 to 600 ohms) 1 MΩ
● 0 to 3000 ohms Yes; 15 bit
● Input resistance (0 to 3000 ohms) 1 MΩ
● 0 to 6000 ohms Yes; 15 bit
● Input resistance (0 to 6000 ohms) 1 MΩ
● PTC Yes; 15 bit
● Input resistance (PTC) 1 MΩ
Thermocouple (TC)
Temperature compensation
— parameterizable Yes
— Reference channel of the module Yes
— internal comparison point Yes; with BaseUnit type A1
— Reference channel of the group Yes
— Number of reference channel groups 4; Group 0 to 3
— fixed reference temperature Yes

Cable length

● shielded, max. 200 m; 50 m with thermocouples
Analog value generation for the inputs
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Basic conversion time, including integration time (ms)
— additional processing time for wire-break check 2 ms; In the ranges resistance thermometers, resistors and thermocouples

2 ms; for 3/4 wire transducer (resistance thermometer and resistor)

— additional power line wire-break check
● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 Hz
● Conversion time (per channel) 180 / 60 / 50 ms
Smoothing of measured values
● Number of smoothing levels 4; None; 4/8/16 times
● parameterizable Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %; ±0.1 % for resistance thermometers and resistance
Temperature error (relative to input range), (+/-) 0.0009 %/K; ±0.005 % / K at thermocouple
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.1 %
● Resistance, relative to input range, (+/-) 0.1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.05 %
● Resistance, relative to input range, (+/-) 0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● Common mode voltage, max. 10 V
● Common mode interference, min. 90 dB

Isochronous mode

Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes

Yes; two upper and two lower limit values in each case

● Limit value alarm
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; channel by channel
● Group error Yes
● Overflow/underflow Yes; channel by channel
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green PWR LED
● Channel status display Yes; Green LED
● for channel diagnostics Yes; Red LED
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes

Isolation

Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
last modified: 01/20/2020

SIEMENS Analog Input Module 6ES7134-6JD00-0CA1