Digital Input Module 6ES7131-6BH00-0BA0 SIEMENS
*** Spare part *** SIMATIC ET 200SP SIEMENS , digital input module, DI 16X 24 V DC Standard, suitable for BU type A0, color code CC00, module diagnostics
SIEMENS | |||
General information |
|||
Product type designation | DI 16×24 VDC ST | ||
Firmware version
● FW update possible |
V1.1 | ||
Yes | |||
usable BaseUnits | BU type A0 | ||
Color code for module-specific color identification plate | CC00 | ||
Product function | |||
● I&M data | Yes; I&M0 to I&M3 | ||
Engineering with | |||
● STEP 7 TIA Portal configurable/integrated as of version | V13 SP1 | ||
● STEP 7 configurable/integrated as of version | V5.5 / –
|
||
● PCS 7 configurable/integrated as of version | |||
● PROFIBUS as of GSD version/GSD revision | |||
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | ||
Operating mode | |||
● DI | Yes | ||
● Counter | No |
● Oversampling | No
No |
● MSI | |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption, max. | 90 mA |
Encoder supply | |
Short-circuit protection | No |
24 V encoder supply | |
● 24 V | No |
● Short-circuit protection | No |
Power loss | |
Power loss, typ. | 1.7 W |
Address area | |
Address space per module | |
● Address space per module, max. | 2 byte; + 2 bytes for QI information |
Hardware configuration | |
Automatic encoding | |
● Mechanical coding element | Yes |
Selection of BaseUnit for connection variants | |
● 1-wire connection | BU type A0 |
● 2-wire connection | BU type A0 + external terminals |
● 3-wire connection | BU type A0 + external terminals |
● 4-wire connection | BU type A0 + external terminals |
Digital inputs |
|
Number of digital inputs | 16 |
Source/sink input | P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input characteristic curve in accordance with IEC 61131, type 2 | No |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Pulse extension | No |
Input voltage | |
● Rated value (DC) | 24 V |
● for signal “0” | -30 to +5 V |
● for signal “1” | +11 to +30V |
Input current | |
● for signal “1”, typ. | 2.5 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
— parameterizable | Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) |
— at “0” to “1”, min. | 0.05 ms |
— at “0” to “1”, max. | 20 ms |
— at “1” to “0”, min. | 0.05 ms |
— at “1” to “0”, max. | 20 ms |
for interrupt inputs | |
— parameterizable | No |
for technological functions | |
— parameterizable | No |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Encoder |
|
Connectable encoders | |
● 2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Alarms | |
● Diagnostic alarm | Yes |
Diagnostic messages | |
● Diagnostic information readable | Yes |
● Monitoring the supply voltage | Yes |
— parameterizable | Yes |
● Monitoring of encoder power supply | No |
● Wire-break | Yes; Module-by-module, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm |
● Short-circuit | No |
● Group error | Yes |
Diagnostics indication LED |