Analog Input Module 6ES7134-6JD00-0CA1
SIMATIC SIEMENS ET 200SP, Analog input module , AI 4xRTD/TC High Feature, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.1%, 2-/3-/4-wire
SIEMENS | |
General information |
|
Product type designation | AI 4x RTD/TC 2/3/4-wire HF, PU 1 |
HW functional status | From FS08 |
Firmware version
● FW update possible |
Yes |
usable BaseUnits | BU type A0, A1 |
Color code for module-specific color identification plate | CC00 |
Product function | |
● I&M data | Yes; I&M0 to I&M3 |
● Adjustment of measuring range | Yes |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated as of version | V14 |
● STEP 7 configurable/integrated as of version | V5.6 |
● PCS 7 configurable/integrated as of version | V8.1 SP1 |
● PROFIBUS as of GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 |
Operating mode |
● Oversampling | No
No |
● MSI | |
CiR – Configuration in RUN | |
Reparameterization possible in RUN | Yes |
Calibration possible in RUN | Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption, max. | 35 mA |
Power loss | |
Power loss, typ. | 0.75 W |
Address area |
|
Address space per module | |
● Address space per module, max. | 8 byte; + 1 byte for QI information |
Hardware configuration | |
Automatic encoding | Yes |
● Mechanical coding element | Yes |
Selection of BaseUnit for connection variants | |
● 2-wire connection | BU type A0, A1 |
● 3-wire connection | BU type A0, A1 |
Analog inputs |
|
Number of analog inputs | 4 |
permissible input voltage for voltage input (destruction limit), max. | 30 V |
Cycle time (all channels), min. | Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary |
Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
Input ranges (rated values), voltages | |
● -1 V to +1 V | Yes; 16 bit incl. sign |
● Input resistance (-1 V to +1 V) | 1 MΩ |
● -250 mV to +250 mV | Yes; 16 bit incl. sign |
● Input resistance (-250 mV to +250 mV) | 1 MΩ |
● -50 mV to +50 mV | Yes; 16 bit incl. sign
1 MΩ |
● Input resistance (-50 mV to +50 mV) |
● Input resistance (Ni 500) | 1 MΩ
Yes; 16 bit incl. sign |
● Pt 100 | |
● Input resistance (Pt 100) | 1 MΩ |
● Pt 1000 | Yes; 16 bit incl. sign |
● Input resistance (Pt 1000) | 1 MΩ |
● Pt 200 | Yes; 16 bit incl. sign |
● Input resistance (Pt 200) | 1 MΩ |
● Pt 500 | Yes; 16 bit incl. sign |
● Input resistance (Pt 500) | 1 MΩ |
Input ranges (rated values), resistors | |
● 0 to 150 ohms | Yes; 15 bit |
● Input resistance (0 to 150 ohms) | 1 MΩ |
● 0 to 300 ohms | Yes; 15 bit |
● Input resistance (0 to 300 ohms) | 1 MΩ |
● 0 to 600 ohms | Yes; 15 bit |
● Input resistance (0 to 600 ohms) | 1 MΩ |
● 0 to 3000 ohms | Yes; 15 bit |
● Input resistance (0 to 3000 ohms) | 1 MΩ |
● 0 to 6000 ohms | Yes; 15 bit |
● Input resistance (0 to 6000 ohms) | 1 MΩ |
● PTC | Yes; 15 bit |
● Input resistance (PTC) | 1 MΩ |
Thermocouple (TC) | |
Temperature compensation | |
— parameterizable | Yes |
— Reference channel of the module | Yes |
— internal comparison point | Yes; with BaseUnit type A1 |
— Reference channel of the group | Yes |
— Number of reference channel groups | 4; Group 0 to 3 |
— fixed reference temperature | Yes |
Cable length |
|
● shielded, max. | 200 m; 50 m with thermocouples |
Analog value generation for the inputs | |
Measurement principle | integrating (Sigma-Delta) |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 16 bit |
● Integration time, parameterizable | Yes |
● Basic conversion time, including integration time (ms) |
— additional processing time for wire-break check | 2 ms; In the ranges resistance thermometers, resistors and thermocouples
2 ms; for 3/4 wire transducer (resistance thermometer and resistor) |
— additional power line wire-break check | |
● Interference voltage suppression for interference frequency f1 in Hz | 16.6 / 50 / 60 Hz |
● Conversion time (per channel) | 180 / 60 / 50 ms |
Smoothing of measured values | |
● Number of smoothing levels | 4; None; 4/8/16 times |
● parameterizable | Yes |
Encoder | |
Connection of signal encoders | |
● for voltage measurement | Yes |
● for resistance measurement with two-wire connection | Yes |
● for resistance measurement with three-wire connection | Yes |
● for resistance measurement with four-wire connection | Yes |
Errors/accuracies | |
Linearity error (relative to input range), (+/-) | 0.01 %; ±0.1 % for resistance thermometers and resistance |
Temperature error (relative to input range), (+/-) | 0.0009 %/K; ±0.005 % / K at thermocouple |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range | |
● Voltage, relative to input range, (+/-) | 0.1 % |
● Resistance, relative to input range, (+/-) | 0.1 % |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to input range, (+/-) | 0.05 % |
● Resistance, relative to input range, (+/-) | 0.05 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
● Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
● Common mode voltage, max. | 10 V |
● Common mode interference, min. | 90 dB |
Isochronous mode |
|
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Alarms |
● Diagnostic alarm | Yes
Yes; two upper and two lower limit values in each case |
● Limit value alarm | |
Diagnostic messages | |
● Monitoring the supply voltage | Yes |
● Wire-break | Yes; channel by channel |
● Group error | Yes |
● Overflow/underflow | Yes; channel by channel |
Diagnostics indication LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; Green PWR LED |
● Channel status display | Yes; Green LED |
● for channel diagnostics | Yes; Red LED |
● for module diagnostics | Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
● between the channels | No |
● between the channels and backplane bus | Yes |
● between the channels and the power supply of the electronics | Yes |
Isolation |
|
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | -30 °C |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | -30 °C |
● vertical installation, max. | 50 °C |
Altitude during operation relating to sea level | |
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
last modified: | 01/20/2020 |
SIEMENS Analog Input Module 6ES7134-6JD00-0CA1