Digital Output Module 6ES7132-6BH00-0BA0
*** Spare part *** SIMATIC ET 200SP, Digital Output Module , DQ 16x 24VDC/0.5A Standard, suitable for BU type A0, Color code CC00, module diagnostics
SIEMENS | |||
General information |
|||
Product type designation | DQ 16×24 VDC/0.5 A ST | ||
Firmware version
● FW update possible |
V1.0 | ||
Yes | |||
usable BaseUnits | BU type A0 | ||
Color code for module-specific color identification plate | CC00 | ||
Product function | |||
● I&M data | Yes; I&M0 to I&M3 | ||
Engineering with | |||
● STEP 7 TIA Portal configurable/integrated as of version | V11 SP2 / V13 | ||
● STEP 7 configurable/integrated as of version | V5.5 SP3 / –
|
||
● PCS 7 configurable/integrated as of version | |||
● PROFIBUS as of GSD version/GSD revision | |||
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | ||
Operating mode | |||
● DQ | Yes | ||
● DQ with energy-saving function | No |
● PWM | No
No |
● Oversampling | |
● MSO | No |
Redundancy | |
● Redundancy capability | Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
|
Current consumption, max. | 60 mA; without load |
Output voltage | |
Rated value (DC) | 24 V |
Power loss | |
Power loss, typ. | 1 W |
Address area | |
Address space per module | |
● Address space per module, max. | 2 byte |
Hardware configuration | |
Automatic encoding | |
● Mechanical coding element | Yes |
Selection of BaseUnit for connection variants | |
● 1-wire connection | BU type A0 |
● 2-wire connection | BU type A0 + Potential isolation module |
● 3-wire connection | BU type A0 + Potential isolation module |
● 4-wire connection | BU type A0 + Potential isolation module |
Digital outputs | |
Type of digital output | Source output (PNP, current-sourcing) |
Number of digital outputs | 16 |
Current-sinking | No |
Current-sourcing | Yes |
Digital outputs, parameterizable | Yes |
Short-circuit protection | Yes |
● Response threshold, typ. | 0.7 to 1.3 A |
Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs |
|
● with resistive load, max. | 0.5 A |
● on lamp load, max. | 5 W |
Load resistance range | |
● lower limit | 48 Ω |
● upper limit | 12 kΩ |
Output current | |
● for signal “1” rated value | 0.5 A |
● for signal “0” residual current, max. | 0.1 mA |
Output delay with resistive load | |
● “0” to “1”, typ. | 50 µs |
● “1” to “0”, typ. | 100 µs |
Parallel switching of two outputs | |
● for uprating | No |
● for redundant control of a load | Yes |
Switching frequency | |
● with resistive load, max. | 100 Hz |
● with inductive load, max. | 2 Hz |
● on lamp load, max. | 10 Hz |
Total current of the outputs | |
● Current per channel, max. | 0.5 A |
● Current per module, max. | 8 A |
Total current of the outputs (per module) | |
horizontal installation | |
— up to 30 °C, max. | 8 A |
— up to 40 °C, max. | 8 A |
— up to 50 °C, max. | 6 A |
— up to 60 °C, max. | 4 A |
vertical installation | |
— up to 30 °C, max. | 8 A |
— up to 40 °C, max. | 6 A |
— up to 50 °C, max. | 4 A |
— up to 60 °C, max. | 4 A |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms | |
● Diagnostic alarm | Yes |
Diagnostic messages | |
● Monitoring the supply voltage | Yes |
● Wire-break | Yes; Module-wise |
● Short-circuit to M | Yes; Module-wise |
● Short-circuit to L+ | Yes; Module-wise |
● Group error | Yes |
Diagnostics indication LED |
|
● Monitoring of the supply voltage (PWR-LED) | Yes; Green PWR LED |
● Channel status display | Yes; Green LED |
● for channel diagnostics | No |
● for module diagnostics | Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
● between the channels | No |
● between the channels and backplane bus | Yes |
● between the channels and the power supply of the electronics | No |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions | No |
Suitable for safety-related tripping of standard modules | Yes; From FS03 |
Highest safety class achievable in safety mode | |
● Performance level according to ISO 13849-1 | PL d |
● SIL acc. to IEC 61508 | SIL 2 |
Ambient conditions | |
Ambient temperature during operation | |
● horizontal installation, min. | 0 °C |
● horizontal installation, max. | 60 °C |
● vertical installation, min. | 0 °C; in all other mounting positions |
● vertical installation, max. | 50 °C; in all other mounting positions |
Altitude during operation relating to sea level | |
● Ambient air temperature-barometric pressurealtitude | On request: Negative ambient temperature down to -30 °C
(without condensation), installation altitudes between 2 000 m and 5 000 m |
Dimensions | |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
SIEMENS Digital Output Module 6ES7132-6BH00-0BA0 |